Permit Number: C17-1141
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location: E06A
Work Description: MINOR TENANT IMPROVEMENT TO INCLUDE ARCH AND ELEC-GJS
Status: Issued
Project Name: COACH
Review Type: Electrical
Result: Correction
Result Date: 3/14/2017 2:51:28 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Electrical Comments



Reviewed by: David Abuobaid                                                Permit
#: C17-1141



Phone: 343-8333                                                                      Date: 3/14/2017



Fax:     249-7775                                                                     



Email:  AbuobaidDH@muni.org



Manager: Andrew Earp    



Phone: 343-8338



Email:  EarpAL@muni.org



Project: COACH (Fax:
no fax provided)



____________________________________________________________________________________



1.  The following comments based on the 2014
National Electrical Code (NEC) must be resolved before a permit is issued. The
approval of plans and specifications does not permit the violation of any
section of the NEC or any federal, state or local regulations.



 



2.  PANEL SCHEDULE:



Sheet E100 (Panel
Schedule). Please provide panel schedule with the following:



(a)  Panel schedule calculated loads and NEC
demand loads.



(b)  Circuit directory / identification as required
by NEC section 408.4.



(c)  Calculated result with the amperage interrupting
ampacity.   



 



3.  EXISTING
SERVICE LOAD CALCULATIONS:

Sheet E100. The plans have no calculations for feeder loads for the existing
building as required by NEC Section 220.87. Please address.



 



4. AVAILABLE FAULT CURRENT:



Sheet E100 (Available Fault Current). Provide calculation for the available fault current at the main service equipment. NEC Section 110.24 requires that service equipment be legibly marked in the field with maximum available fault current. Please address.



 



5.  When the above comments have been addressed,
please update the electrical plans at the MOA Plans Review Office with three
(3) sets of revised electrical pages to include clouded changes, electrical
engineers stamp and signature.    