Permit Number: C17-1089
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location: Suite# 3-130
Work Description: T/I to include demo,plumb,mech,electirc, and merchandise racking - BWP
Status: Closed
Project Name: AMERICAN EAGLE
Review Type: Structural
Result: Correction
Result Date: 3/9/2017 1:32:38 PM

Comments:

 Code SectionReview CommentStatus
1_

1. Provide storage rack plans that have been stamped and sealed by the EOR.

2. Show the minimum attachments, member sizes, connections, anchor bolts, anchor bolt embedment, etc., and other required information as noted in the calculations on the plans.

3. Note that the post installed anchors require special inspection on the plans.

4. Provide a letter from the special inspection agency that will be performing the special inspection of the post installed anchors. 

5. Provide the aluminum storefront design for review as a deferred submittal - note this on the plans.

6. Please respond to each item in writing. Please note that additional comments may be made based on the responses received.