Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C17-1089
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location: Suite# 3-130
Work Description: T/I to include demo,plumb,mech,electirc, and merchandise racking - BWP
Status: Closed
Project Name: AMERICAN EAGLE
Review Type: Fire
Result: Correction
Result Date: 3/12/2017 8:23:21 AM

Comments:

 Code SectionReview CommentStatus
1_
Refer to Sheet A.0.010, General Note 34. Plans shall indicate the location(s) and rating(s) of fire extinguisher(s) serving each space.
Reference: IFC Section 906.3


2_
Refer to Sheet A.0.100, E.0.100. The common path travel distance from the most remote fitting room exceeds 75 ft., requiring two exits. No signage is shown for exiting through Passageway 6a. Clarify the second exit, or revise exit signage accordingly.
Reference: IFC Section 1011.1, 1015.1


3_
Refer to Sheet A.0.100. Door 4e is noted as an exit and appears to serve more than 50 occupants. The door swing needs to be revised.
Reference: IFC Section 1008.1.2


4_
Refer to Sheets A.0.106, A.1.900. Please clarify whether there will be high-piled storage within the stockroom areas; ceiling elevations are not provided in this area and the shelving heights shown could facilitate top of commodity at 12 ft.
Reference: IFC Section 105.4.2, 3201.1





Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter