Permit Number: C17-1087
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 790 DIMOND BLVD Anchorage
Location:
Work Description:

INTERIOR AND EXTERIOR ALTERATION.  RETROFIT EXISTING TRANSIT CENTER BUILDING, IMPROVE VEHICULAR CIRCULATION, IMPROVE PEDESTRIAN CIRCULATION, IMPROVE DRAINAGE, IMPROVE SITE LIGHTING AND IMPROVE LANDSCAPING - MJD

CONTRACTOR TO PAY FOR INSPECTIONS- CONTRACTOR PAID FOR 10 INSPECTIONS AND STORM WATER FEES ON 7-19-17-SM/ CHANGE ORDER ISSUED TO CCE + ELECTRICAL AS PARTIAL PERMIT-GJS

Status: Closed
Project Name: DIMOND INTERMODAL FACILITY PROJECT
Review Type: Fire
Result: Correction
Result Date: 3/10/2017 3:31:10 PM

Comments:

 Code SectionReview CommentStatus
1_
Refer to Sheet 65. The architectural code study for the transit canopy and concession kiosk does not include the roof area of the canopy. This will need to be included in the building area calculation. Please update accordingly.
Reference: IFC Section 105.4.2, 202 "Area, Building"; IBC Section 503.1


2_
Refer to Sheet 69. Please provide the location of the Knox Box to the right of the entry doors, installed no higher than 60 in. above walking surface.
Reference: IFC Section 506.1


3_
Please clarify the location(s) of the fire extinguishers accessible to the waiting area. It appears the FE shown in the room adjacent concessions may be in a secured space.
Reference: IFC Section 906.3