INTERIOR AND EXTERIOR ALTERATION. RETROFIT EXISTING TRANSIT CENTER BUILDING, IMPROVE VEHICULAR CIRCULATION, IMPROVE PEDESTRIAN CIRCULATION, IMPROVE DRAINAGE, IMPROVE SITE LIGHTING AND IMPROVE LANDSCAPING - MJD
CONTRACTOR TO PAY FOR INSPECTIONS- CONTRACTOR PAID FOR 10 INSPECTIONS AND STORM WATER FEES ON 7-19-17-SM/ CHANGE ORDER ISSUED TO CCE + ELECTRICAL AS PARTIAL PERMIT-GJS
Architectural Comments
Reviewed by: David Abuobaid Permit#: C17-1087
Phone: 343-8333 Date: 3/132017
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Melissa Davidson
Phone: 343-8339
Email: davidsonmj@muni.org
Project: DimondIntermodel (Fax: no fax # provided)
____________________________________________________________________________________
1. The following comments based upon the 2012International Building Code (IBC) must be resolved before a permit is issued.The approval of plans and specifications does not permit the violation of anysection of the IBC or any federal, state or local regulations.
2. TOILET FACILITIES:
Sheet66 of 74. There is only one ADA bathroom. Please provide location, traveldistance, and code compliance for the restrooms facilities as required by IBCsection and table 2902.1
3. When the above comments have been addressedplease update the plans at the MOA Plans Review Office with three sets ofrevised architectural pages to include clouded changes, engineers stamp andsignature.