Click Here To Go Back To Permit Information
Permit Number:
X17-1099
Permit Type:
Commercial Building Permit - ChangeOrdr BldgNew
Address:
Location:
Work Description:
Change order to S/A/P/M/E/F/Z - BWP
Status:
Closed
Project Name:
Change Order of Bldg App C15-1806
Review Type:
Fire
Result:
Correction
Result Date:
3/15/2017 12:29:00 PM
Comments:
Code Section
Review Comment
Status
1
_
ADVISORY - Refer to Sheet G003. Please note that fire systems (sprinkler/standpipe, FDC, alarm) require separate fire systems permits. Review of the fire alarm plans submitted under this cover is cursory for general requirements.
Reference: IFC Section 105.4.2; AFD Policy 08-014 (http://www.muni.org/Departments/Fire/Prevention/Documents/handout014.pdf)
2
_
Refer to Sheets A020, A052, A101a. The code plan is not reflective of the new patio area as well as exiting through a single door (Door 71/017) after exiting through double doors (Door 018). Please clarify the exiting. Please also note the discrepancy in door labels between Sheets A052 and A101a for the patio door.
Reference: IFC Section 105.4.2, 1003.6
3
_
Refer to Sheets A020, A052, A572. The code study notes the construction type as Type V-A. The patio and trellis framing do not show any fire-resistive construction. Please clarify the protection of the primary and secondary combustible construction.
Reference: IFC Section 701.1; IBC Section 602.1
4
_
Refer to Sheets A052, A572. Please clarify the separation from the firepit to the face of the trellis construction. None of the plans provide any dimensions from Grid H.
Reference: IFC Section 308.3, 308.4
5
_
Refer to Sheets A101a, E2.1L. Please address the following:
a. The egress through Door 018 does not appear to have adequate emergency egress lighting once under the patio roof. Please clarify.
b. There are no directional exit signs in the patio area for Door 018 or 17c. Please clarify the location(s) for exiting to Door 017.
Reference: IFC Section 1006.3, 1011.1
6
_
Refer to Sheet F2.11. The location of the fire alarm annunciator panel behind the reception desk will need to be relocated to the entry vestibule.
Reference: IFC Section 907.2; NFPA 72 10.16.3.2