Drawing A600, Door Schedule; Are the Toilet Room Doors shown as 028 and 029 intended to not be 20 minute Fire Resistant rated per IBC Table 1018.1? Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A020, Code Plans, Section 1, 1st Floor Code Plan; and preceding comment 6.
Drawing A600, Door Schedule; Is the Work Room Door shown as 036 intended to not be 20 minute Fire Resistant rated per IBC Table 1018.1? Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A020, Code Plans, Section 1, 1st Floor Code Plan; and preceding comment 6.
Drawing A600, Door Schedule; Is the Electrical Room Door shown as 040a inadvertently missing from the Door Schedule. Additionally, is this Electrical Room Door shown as 040a intended to not be 20 minute Fire Resistant rated per IBC Table 1018.1? Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A020, Code Plans, Section 1, 1st Floor Code Plan; and preceding comment 6.
Drawing A600, Door Schedule; Are the Stair Exit Enclosure Doors shown as 050b and 051b intended to not be 90 minute Fire Resistant rated per IBC Section 1027.7? Refer to Drawing A101a, Main Level Floor Plan - Area A; Drawing A101b, Main Level Floor Plan - Area B; and Drawing A020, Code Plans, Section 1, 1st Floor Code Plan. Please clarify.
Drawing A600, Door Schedule; The Door Schedule includes a Closet Door shown as 052. Is the Closet Door shown as 052 inadvertently missing from the Plans? Refer to Drawing A101a, Main Level Floor Plan - Area A and Drawing A101b, Main Level Floor Plan - Area B.
Drawing A600, Door Schedule; Is the Stair Exit Enclosure Door shown as 550 intended to not be 90 minute Fire Resistant rated per IBC Section 1027.7? Refer to Drawing A105, Roof Plan. Please clarify.
Drawing A101a, Main Level Floor Plan - Area A; Drawing A101b, Main Level Floor Plan - Area B; and Drawing A020, Code Plans, Section 1, 1st Floor Code Plan; Since the Courtyard is not sufficiently far enough away from the hotel, please verify that Door 071 has the required egress width. Two doors may be required, unless you can show the adequacy of this exit. Please clarify.