Permit Number: C16-2005
Permit Type: Commercial Building Permit - None BldgNew
Address: E 1713 64TH AVE Anchorage
Location:
Work Description:

Work to include Architectural, Structural, Fire, Electrical, Plumbing, and Mechanical.

S-1 : 18360 sqft - AJC  REASSIGNED TO ANDREW 11/16/16

FINAL FIRE INSPECTION SAME DAY INSPECTION FEE PAID FOR C16-2006 UNDER THIS PERMIT - RED & GS 6/28/2019


Status: Closed
Project Name: DOWLING WAREHOUSE RENTALS BLDG A
Review Type: Structural
Result: Correction
Result Date: 2/3/2017 3:51:17 PM

Comments:

 Code SectionReview CommentStatus
1_

Metal Building:


1. Provide "For Construction/Erection" drawings. Comment remains 2/3/2017 - No updated sheets found per the response.

2. Provide minimum pretension requirements for the high strength bolts, on the plans. See ASCE section J3. Comment remains 2/3/2017 - Sheet not updated with information, per the response.

3. See AISC 341, section D2.2. See number (2), and detail D/4, please provide design of this connection, additionally the calculations appear to specify 1" diameter rod, but the detail  and the end brace(between 1 and 2) shows 3/4". See number (3), Indicate hole type/size in the bolted connections, revise calculations as necessary. See number (4), Indicate required faying surfaces on the plans of connections of the LFRS per AISC 360 section J3.8. Comment remains 2/3/2017 - Sheet not updated with information, per the response.

4. See sheet 3.

  a. Provide diagonal brace connection design and details. Comment remains 2/3/2017 - Sheet not updated with information, per the response.

5. See sheet 5.

  a. Resolved 2/3/2017


 



2_

Provide letter from special inspection agency who will perform the special inspections.


Comment remains. 12/21/2016


Comment remains 2/3/2017