Reviewed by: Bergstrom, Leigh W.
Phone: 343-8326
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Melissa Davidson
Phone: 343-8339
Email: DavidsonMJ@muni.org
Project: DAVE & BUSTERS
Review Number: 383829
1) STATUS: 9-26-2016 Comments to be addressed. 12-20-2016 APPROVED.
2) The following comments based upon the 2012 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. RESOLVED 12-20-2016.
3) 1/M2.0 The 1-1/2" V serving P-1A, P-4 & FD-1 is undersized per UPC Table 703.2 note #3. RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.
4) M2.1 With reference to note #3, clarify how a second floor waste line that is located 15 feet AFF can serve the plumbing fixtures on that floor. RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.
5) M2.1 Clarify on the plans that the vent piping from the first floor bathrooms is not to pass through nor penetrate the membrane of the rated assemblies surrounding the stairwell. (IBC 1022.5) RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.
6) M2.2 The gas branch that provides 3,450 MBH to the second floor tenant lease space is missing (Ref 1/M3.1). RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.
7) 5/M3.1 When discharging to the exterior of a building the discharge point shall be labeled "Elevator Pit Discharge" per MOA policy L.02. RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.
8) 1/M3.1 Clarify the 2# gas supply branch sizes serving RTU-15 and the tenant lease space at 3450 MBH. RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.
9) 1/M3.1 The total load on the gas meter is 9,706 MBH (2 locations). RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.
10) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1) RESOLVED 12-20-2016.