Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-1933
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: RAISING ROOF TO MEET DAVE & BUSTERS REQUIREMENTS.  EXTENDING SOUTH 2ND FLOOR EXTERIOR WALL TO BE INLINE WITH 1ST FLOOR EXTERIOR WALL.  TO INCLUDE PLUMBING, MECHANICAL & ELECTRICAL.  47,067 SQFT - MJD
Status: Closed
Project Name: DAVE & BUSTERS
Review Type: Plumbing
Result: Approved
Result Date: 12/20/2016 8:43:08 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Melissa Davidson

Phone: 343-8339

Email: DavidsonMJ@muni.org

Project: DAVE & BUSTERS

Review Number: 383829


1) STATUS: 9-26-2016 Comments to be addressed.                  12-20-2016 APPROVED.


2) The following comments based upon the 2012 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.                    RESOLVED 12-20-2016.


3) 1/M2.0              The 1-1/2" V serving P-1A, P-4 & FD-1 is undersized per UPC Table 703.2 note #3.              RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.


4)  M2.1                With reference to note #3, clarify how a second floor waste line that is located 15 feet AFF can serve the plumbing fixtures on that floor.                                RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.


5) M2.1                 Clarify on the plans that the vent piping from the first floor bathrooms is not to pass through nor penetrate the membrane of the rated assemblies surrounding the stairwell. (IBC 1022.5)                     RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.


6) M2.2                 The gas branch that provides 3,450 MBH to the second floor tenant lease space is missing (Ref 1/M3.1).           RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.


7) 5/M3.1              When discharging to the exterior of a building the discharge point shall be labeled "Elevator Pit Discharge" per MOA policy L.02.               RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.


8) 1/M3.1              Clarify the 2# gas supply branch sizes serving RTU-15 and the tenant lease space at 3450 MBH.                        RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.


9) 1/M3.1              The total load on the gas meter is 9,706 MBH (2 locations).                            RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.


10) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)                RESOLVED 12-20-2016.