Permit Number: C16-1933
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: RAISING ROOF TO MEET DAVE & BUSTERS REQUIREMENTS.  EXTENDING SOUTH 2ND FLOOR EXTERIOR WALL TO BE INLINE WITH 1ST FLOOR EXTERIOR WALL.  TO INCLUDE PLUMBING, MECHANICAL & ELECTRICAL.  47,067 SQFT - MJD
Status: Closed
Project Name: DAVE & BUSTERS
Review Type: Mechanical
Result: Approved
Result Date: 12/20/2016 8:45:57 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Melissa Davidson

Phone: 343-8339

Email: DavidsonMJ@muni.org

Project: DAVE & BUSTERS

Review Number: 383800


1) STATUS: 9-26-2016 Comments to be addressed.                12-20-2016 APPROVED.


2) The following comments based upon the 2012 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.               RESOLVED 12-20-2016.


3) Provide structural, seismic and wind load calculations as applicable, plus fastening details for RTU-1 thru 17, MAU-1 & 2, EH-2 and WH-1 to include the engineers stamp and signature for structural review on a deferred submittal basis.            RESOLVED 12-20-2016.


4) M2.1               Clarify on the plans that the ductwork for EF-4 is not to pass through nor penetrate the membrane of the rated assemblies surrounding the stairwell. (IBC 1022.5)           RESOLVED PER RE-SUBMITTAL RECEIVED 12-19-2016.


5) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)             RESOLVED 12-20-2016.