Permit Number: C16-2065
Permit Type: Commercial Building Permit - None BldgAlter
Address: 5600 DEBARR RD Anchorage
Location:
Work Description:

ENCLOSE BY METAL FRAMING SMALL WALLS, FINISH DRY WALL AND FRP.  INSTALL ACOUSTICAL CEILING W/WASHABLE TILES, NEW STRIP LIGHTING AND OUTLET COVERS, REFRIDGE COIL UNIT TIE INTO EXISTING SYSTEM,

INSTALL VINYL STRIP DOOR, MMA FLOOR SYSTEM, TABLES, SHELVES, AND EQUIPMENT-SP.

Status: Closed
Project Name: SAFEWAY STORE 27-1809
Review Type: Structural
Result: Correction
Result Date: 12/13/2016 11:02:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Structural Comments



 



Reviewed by: Hellman, Becky A.                                               Permit
#: C16-2065



Phone: 343-8237                                                                      
               Second Review     



Fax: 249-7400                                                         
                       
Date: 12-13-16



Email: hellmanba@muni.org



Permit Manager: Sean Palmer



Phone: 343-8181



Email: palmersp@muni.org



Project: East Gate
Lot 2C BLK 1A – 5600 Debarr Rd. – Safeway Alteration



 



____________________________________________________________________________________



Plan review
comments:



 



1.  This review is a
code compliance review based on the requirements of the 2012 International
Building Code (IBC) and all adopted references thereto as amended by the
Municipality of Anchorage in the Anchorage Municipal Code (AMC) Title 23.  This review does not permit the violation of
the building codes, nor any federal, state, or municipal regulation.



 



2.  The description of work is not
clear for the structural aspect of this project.  What structurally is new? I see a 4” framed
column being identified, but that is it. 
Is this 4” column the only thing that is supporting the new vinyl
curtains; header, fastening, right side attachment; all should be checked for
out of plan internal wind pressures? Please provide information on the
support/construction of the new curtain. 



 



12-13-16   Calculations accepted.  Please provide detail for the lateral support
of the columns on either side of the header; there is an out of plane lateral
load that needs to be resisted.



 



3.  A wall section was provided on
sheet A101.  Is this a new wall? Where is
it going?  Are walls being replaced? Or
only finishes?  Please clarify on the
plan where this wall section is being constructed.  This wall section is required to have a
registered licensed Architect or Engineer stamp.



 



12-13-16   Not addressed. 
What will this wall section be used for?



 



Address all comments above to complete the permit process.  Please provide corresponding letter that
describes how comments have been addressed and where on the plans the changes
have occurred.  Any additional
information that is provided to address the above comments could result in
additional comments based on the new information provided for review.   All
submittals should be sent or given to the permit manager for this project.



 