Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-2138
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location: Unit# 3-227
Work Description: Unit# 3-227 - Comm T/I to include plumb/mech/electric - BWP
Status: Closed
Project Name: CALI NAILS
Review Type: Mechanical
Result: Correction
Result Date: 12/2/2016 12:57:07 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker

Phone: 343-8391

Email: ParkerRW@muni.org

Project: CALI NAILS

Review Number: 383188


1) STATUS: 12-02-2016 Comments to be addressed.


2) The following comments based upon the 2012 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. 


3) M-200                  The open working area is approximately 1,200 square feet. IMC Table 403.3 requires .6 CFM per square foot of exhaust direct to the exterior for nail salons. This would be 720 CFM or 120 CFM shy of what EF-1 can provide. The rooftop unit is not allowed to make up the deficit since the air cannot be part of a recirculating system per Table 403.3 footnote 'b".


4) M-200                 Provide clarification that  the existing ventilation system is a stand alone unit for this tenant space only. (IMC 403.2.1 exception #1)


5) M-200                 Clarify the makeup air path for the laundry room when the clothes dryer is operating.


6) M-200                 The quick dry tables also require source capture exhaust  per Table 403.3 plus local amendment.


7) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter