Pre-Approved, pending approval of C16-2005. Mirrored plans of C16-2005. Work to include Architectural, Structural, Fire, Electrical, Plumbing, and Mechanical.S-1 : 18360sqft - AJC
Comments on 12-01-16 resubmittal
1. Provide haul route information to and from proposed import and export locations. Identify the proposed import and export locations. Response indicates that contractor to provide prior receiving a permit. Comment Remains 12-5-16~RR
2. Provide recorded snow management agreement with municipality for alternative snow management solution. Contact Sonnet Calhoun in Planning for application. Response indicate that an agreement will be obtained, Comment Remains 12-5-16~RR
3. Sheet C4.0 - Provide additional sheet notes to the plan. A) All pavementmarkings shall be painted with 4" white striped unless otherwise noted. B) All accessible parking spaces shall be painted with 4" blue stripes. All curb /wheel stops to be painted blue for accessible space. No additional information provided. 12-5-16~RR (Sheet C4.0 not replaced in thefield set).
4. Sheet C4.0- Provide an R&P-101 "No Parking Anytime" for the van accessible aisles. Add sign information to sign stable. Indicate location of these signs on the plan. No additional information provided. 12-5-16~RR, (Sheet C4.0 not replaced in the field set).
5. Sheet C4.0 -Provide Dimensions to include width and radius information for driveway connection to East 64th Avenue. No additional information provided. 12-5-16~RR, (Sheet C4.0 not replaced in the field set).
6. Sheet C4.0 - Class A loading berths shown. Please provide information that demonstrates turning and maneuverability for a semi-truck vehicle. Response provided does not address the comment. Provide requested information demonstrating maneuverability of WB-50 or obtain approval from Municipal Traffic Engineer on reduction in type of loading berths required, or provide additional information to zoning to resolve warehouse classification. Comment Remains 12-5-16~RR. (Sheet C4.0 not replaced in the field set).
7. Sheet L1.0 - Show sight distance triangles for driveway at East 64th Avenue. No additional informationprovided. 12-5-16~RR
~Traffic comments are incomplete. Additional comments may be provided with future resubmittals. ~12-5-16