Permit Number: E16-2069
Permit Type: Commercial Trade Permit - Alteration Electrical
Address: E 401 6TH AVE Anchorage
Location:
Work Description: NOPR - Replace transfer on emergency generator - BWP 
Status: Expired
Project Name: NOPR - 401 E. 6th Ave
Review Type: Fire
Result: Correction
Result Date: 12/7/2016 8:16:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1. Existing one line diagram and modified one line diagram do not match how the system is wired. The fire pump does not come off of the ATS. Provide updated drawings showing proper connected equipment.

2. Drawings do not show connections to the fire alarm system for new ATS. Wires are currently coiled in the new ATS and have not been connected to the fire alarm system for the 5 points being monitored.

3. Drawing do not show how the wiring interfaces for the shunt trip breaker when the emergency generator running and fire pump running.

4. New ATS runs Emergency and Standby loads. This requires a 2nd ATS to be installed.