Electrical Comments
Reviewed by: David Abuobaid Permit #: E16-2067
Phone: 343-8333 Date:12/14/2016
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Bob Parker
Phone: 343-8391
Email: Parkerrw@muni.org
Project: SheratonHotel (Fax: 457-4201)
____________________________________________________________________________________
NOTE – The following commentsare based on the fire department inspection plan review and inspection. Theprevious approval was based on incomplete electrical engineering drawing. Thefire plan review comments need to be addressed.
1. Thefollowing comments based on the 2014 National Electrical Code (NEC) must beresolved before a permit is issued. The approval of plans and specificationsdoes not permit the violation of any section of the NEC or any federal, stateor local regulations.
2. ONE LINE DIAGRAM:
Sheet E-1.The fire planreview \ inspection noted in their report that the existing and revised linediagram do not match.
(a) Provide complete line diagram for the existingand new revised plans. The revised diagram must should show transfer switches,fire pump(s) and their wiring be in compliance with the current NEC code.
(b) Provide panelsschedule for the emergency and standby panels.
(c) Providedetails wiring for the transfer switchers at the source.
(d) The review will continue after receipt of yourresponse
3. Whenthe above comments have been addressed, please update the electrical plans atthe MOA
Plans Review Office with three (3) sets ofrevised electrical pages to include clouded changes, electrical engineers stampand signature.