Permit Type: Commercial Building Permit - None BldgNew
Address: E 1713 64TH AVE Anchorage
Location:
Work Description:

Work to include Architectural, Structural, Fire, Electrical, Plumbing, and Mechanical.

S-1 : 18360 sqft - AJC  REASSIGNED TO ANDREW 11/16/16

FINAL FIRE INSPECTION SAME DAY INSPECTION FEE PAID FOR C16-2006 UNDER THIS PERMIT - RED & GS 6/28/2019


Status: Closed
Project Name: DOWLING WAREHOUSE RENTALS BLDG A
Review Type: Fire
Result: Approved
Result Date: 12/1/2016 2:15:44 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Refer to Sheet C4.0. Please clarify the fire department access around the building. It does not appear that all points on the building are within 150 ft. of the fire lanes, especially on the east side where the grade may not be readily traversable.
Reference: IFC Section 503.1.1

12/1/16 - Resolved. Additional distance approved by Fire Marshal // PANILO


2_Resolved
Refer to Sheet C4.0. The proposed snow storage and loading berth appear to impinge on the fire lane turnaround at the north end of the lot. Please revise.
Reference: IFC Section 503.4

12/1/16 - Resolved. Updated plans show clear fire lanes // PANILO


3_Resolved
Refer to Sheet G1.0, A3.0. Please clarify for the Group S-1 occupancy if there is high-piled storage.
Reference: IFC Section 105.4.2, 3201.1

12/1/16 - Resolved. HPS to be determined at tenant improvement stage; architect advised on concerns to be relayed to owner // PANILO


4_Resolved
Refer to Sheet A2.0. The Knox Box shown on the east elevation is located too high; the maximum installation height is 5 ft. (60 in.). Please revise.
Reference: IFC Section 506.1

12/1/16 - Resolved. Updated plans show revised Knox Box installation height // PANILO


5_Resolved
ADVISORY:
Refer to Sheet A1.0. The travel distance to the fire extinguishers for the larger lease spaces may exceed 75 ft. depending on layout. It is advised that an additional FE be shown to address travel distance.
Reference: IFC Section 906.3

12/1/16 - Architect advised on issue with layout for fire extinguisher travel distance; will relay information to owner. Additional FE may be required at tenant improvement // PANILO