Permit Type: Commercial Building Permit - None BldgAlter
Address: 5600 DEBARR RD Anchorage
Location:
Work Description:

ENCLOSE BY METAL FRAMING SMALL WALLS, FINISH DRY WALL AND FRP.  INSTALL ACOUSTICAL CEILING W/WASHABLE TILES, NEW STRIP LIGHTING AND OUTLET COVERS, REFRIDGE COIL UNIT TIE INTO EXISTING SYSTEM,

INSTALL VINYL STRIP DOOR, MMA FLOOR SYSTEM, TABLES, SHELVES, AND EQUIPMENT-SP.

Status: Closed
Project Name: SAFEWAY STORE 27-1809
Review Type: Fire
Result: Correction
Result Date: 11/18/2016 10:13:36 AM

Comments:

 Code SectionReview CommentStatus
1_
The partition wall sketch shows CDX plywood on one side. Please clarify the use by either defining the construction type as permitting combustible construction, or revise showing fire-retardant treated plywood.
Reference: IBC Section 603.1