Permit Number: C16-2030
Permit Type: Commercial Building Permit - None BldgAlter
Address: 4000 CREDIT UNION DR Anchorage
Location:
Work Description: 6TH FLOOR INTERIOR TI - MJD
Status: Closed
Project Name: ALASKA USA HEADQUARTERS 6TH FLOOR
Review Type: Fire
Result: Approved
Result Date: 11/14/2016 11:36:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Refer to Sheet A-1. The elevator lobby doors are shown to have access control hardware (e.g. card readers). Please clarify how the system complies with Fire Prevention Policy 13-001, and provide required information.
Reference: IFC Section 1008.1.9.8

11/16/16 - Resolved. Contractor apprised of requirements for lobby access controlled egress requirements // PANILO


2_Resolved
Refer to Sheet A-1. The fire extinguisher cabinet shown at the southwest stair appears to be penetrating the exterior exit enclosure membrane. Please clarify how this is being protected.
Reference: IBC Section 1022.5

11/16/16 - Resolved. Exiting FEC; verify current tags // PANILO