Permit Number: C16-2017
Permit Type: Commercial Building Permit - More14Days TempBldg
Address: 3425 TERMINAL RD Anchorage
Location:
Work Description: PORT OFFICE TRAILER , PRIME POWER RATED ENGINE-GENERATOR FOR LIGHTS AND HEATING-GJS
Status: Issued
Project Name:
Review Type: Fire
Result: Approved
Result Date: 11/14/2016 11:13:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Please provide basic floor plan and elevation of the trailer. Plans should include premises identification, location of key box, and location and classification of fire extinguisher that serves the trailer and/or generator.
Reference: IFC Section 105.4.2, 505.1, 506.1, 906.1


2_Resolved
Please provide information on the generator fuel tank, including fuel type (e.g. Class IB flammable liquid, Class IIIA combustible liquid, etc.) and volume, containment (primary and secondary), shutoffs, and signage.
Reference: IFC Section 5001.2, 5003.2, 5003.6