Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-2006
Permit Type: Commercial Building Permit - None BldgNew
Address: E 1715 64TH AVE Anchorage
Location:
Work Description:

Pre-Approved, pending approval of C16-2005. Mirrored plans of C16-2005. Work to include Architectural, Structural, Fire, Electrical, Plumbing, and Mechanical.S-1 : 18360sqft - AJC  



Status: Issued
Project Name: DOWLING WAREHOUSE RENTALS BLDG B
Review Type: Fire
Result: Correction
Result Date: 11/14/2016 9:31:40 AM

Comments:

 Code SectionReview CommentStatus
1_
Refer to Sheet C4.0. Please clarify the fire department access around the building. It does not appear that all points on the building are within 150 ft. of the fire lanes, especially on the west side adjacent to Meadow St. where the grade between the road and the building may not be readily traversable.
Reference: IFC Section 503.1.1


2_
Refer to Sheet C4.0. The proposed snow storage and loading berth appear to impinge on the fire lane turnaround at the north end of the lot. Please revise.
Reference: IFC Section 503.4


3_
Refer to Sheet G1.0, A3.0. Please clarify for the Group S-1 occupancy if there is high-piled storage.
Reference: IFC Section 105.4.2, 3201.1


4_
Refer to Sheet A2.0. The Knox Box shown on the east elevation is located too high; the maximum installation height is 5 ft. (60 in.). Please revise.
Reference: IFC Section 506.1


5_
ADVISORY:
Refer to Sheet A1.0. The travel distance to the fire extinguishers for the larger lease spaces may exceed 75 ft. depending on layout. It is advised that an additional FE be shown to address travel distance.
Reference: IFC Section 906.3





Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS