Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-2005
Permit Type: Commercial Building Permit - None BldgNew
Address: E 1713 64TH AVE Anchorage
Location:
Work Description:

Work to include Architectural, Structural, Fire, Electrical, Plumbing, and Mechanical.

S-1 : 18360 sqft - AJC  REASSIGNED TO ANDREW 11/16/16

FINAL FIRE INSPECTION SAME DAY INSPECTION FEE PAID FOR C16-2006 UNDER THIS PERMIT - RED & GS 6/28/2019


Status: Closed
Project Name: DOWLING WAREHOUSE RENTALS BLDG A
Review Type: Structural
Result: Correction
Result Date: 11/15/2016 10:56:51 AM

Comments:

 Code SectionReview CommentStatus
1_
Please provide the design calculations for the pre-engineered metal building.

2_
Please provide a statement of special inspection per 1704.3

3_
Please revise concrete strength per Table 1904.2.

4_
Revise pilaster details 5 and 6 on S2.2 per page 91 of the calculations.

5_
See detail 3 on S3.1. Clarify the drift limits of the steel frame and show the minimum separation from the concrete wall and the frame.

6_
Provide letter from special inspection agency who will perform the special inspections.




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS