Project Name: FAMOUS FOOTWEAR STORE #3586
Review Type: Fire
Result: Approved
Result Date: 11/2/2016 9:24:04 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Refer to Sheet A1.0. The code study notes the construction type as Type II-B. Please note the original construction type for the Dimond Center Tower was Type I-FR (UBC). Please revise accordingly.
Reference: IFC Section 105.4.2

11/2/16 - Resolved. Updated code study provided with revised construction type // PANILO


2_Resolved
Refer to Sheet A1.0. Section IX (sic) of the code study notes no sprinkler modification. Walls have been demolished from this space as well as new ones being added. This will likely require adjustment of coverage requiring a separate systems permit (to be deferred). Please also note that fire alarm modifications will also likely be required and will need a systems permit (also to be deferred).
Reference: IFC Sections 105.7.1, 105.7.6

11/2/16 - Resolved. Note provided on Sheet A1.0 for sprinkler and fire alarm modifications to be submitted under separate permit // PANILO


3_Resolved
Refer to Sheets A2.0, A4.0, E2.0. The plan shows Door D3 as an exit door, but there is no exterior egress lighting. Please provide.
Reference: IFC Section 1006.3 Item 5

11/2/16 - Resolved. Updated Sheet E2.0 shows exterior egress lighting // PANILO


4_Resolved
The plans do not identify the class and location of required fire extinguishers. Please note on the plans. A minimum of (3) 2-A class extinguishers is anticipated based on the occupancy hazard and the area of the tenant space.
Reference: IFC Section 906.1, 906.3, 906.5

11/2/16 - Resolved. Sheet A4.0 notes fire extinguisher requirements (2A:10BC minimum, 75 ft. max. travel distance), to be field verified by inspector // PANILO