Permit Number: C16-1933
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: RAISING ROOF TO MEET DAVE & BUSTERS REQUIREMENTS.  EXTENDING SOUTH 2ND FLOOR EXTERIOR WALL TO BE INLINE WITH 1ST FLOOR EXTERIOR WALL.  TO INCLUDE PLUMBING, MECHANICAL & ELECTRICAL.  47,067 SQFT - MJD
Status: Closed
Project Name: DAVE & BUSTERS
Review Type: Fire
Result: Correction
Result Date: 10/27/2016 9:18:01 AM

Comments:

 Code SectionReview CommentStatus
1_
Refer to Sheet E2.1, E2.2. The exit stair 103A does not appear to have exterior egress lighting. Please clarify.
Reference: IFC Section 1006.3 Item 5