Electrical Comments
Reviewed by: David Abuobaid Permit #: C6-1933
Phone: 343-8333 Date:9/27/2016
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Melissa Davidson Melissa Davidson
Phone: 343-8339
Email: davidsonmj@muni.org
Project: Dave &Busters (Fax: 907-349-9905)
___________________________________________________________________________________
1. Thefollowing comments based on the 2014 National Electrical Code (NEC) must beresolved before a permit is issued. The approval of plans and specificationsdoes not permit the violation of any section of the NEC or any federal, stateor local regulations.
2. EXISTING SERVICE LOAD CALCULATIONS:Sheet E5.0. The plans have no calculations for feeder loads for the existingbuilding as required by NEC Section 220.87. Please address.
3. CIRCUIT DIRECTORY OR CIRCUIT INDENTIFICATIONON FLOOR PLAN & PANEL SCHEDULES:
Sheet E5.0 (PanelSchedules and Floor Plans Circuit Identifications). Panel LS3 has two circuitsnamed rec. Please note that thesecircuits should be individually identified with their locations on floor plansand on the panel schedules according to NEC 408.4 for circuit identifications.
4. When the above comments have been addressed,please update the electrical plans at the MOA Plans Review Office with three(3) sets of revised electrical pages to include clouded changes, electricalengineers stamp and signature.