Permit Number: C16-1725
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 300 DIMOND BLVD Anchorage
Location:
Work Description: Downsize of an existing FedEx Office tenant space. In the space to remain, there will be new interior finishes, new mop sink, new drinking fountain, and relocated lavatories. New drop ceiling, light fixtures, and relocated diffusers. New interior wall partition construction. New equipment, fixtures, and graphics. Work to include Architectural, Plumbing, Mechanical, and Electrical. - AJC
Status: Closed
Project Name: FEDEX OFFICE T/I
Review Type: Plumbing
Result: Approved
Result Date: 9/12/2016 11:06:36 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Alec Cervenka

Phone: 343-8034

Email: CervenkaAJ@muni.org

Project: FEDEX OFFICE T/I

Review Number: 379246



1) STATUS: 7-25-2016 Comments to be addressed.          9-12-2016 APPROVED.      


2) The following comments based upon the 2012 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.           RESOL:VED 9-12-2016.


3) P-1.0               The public use lavatories require an ASSE 1070 point of use mixing valve per UPC 421.2.                RESOLVED PER RE-SUBMITTAL RECEIVED 9-08-2016.


4) P-2.0               Provide an equipment schedule for the electric water heater (EWH).                  RESOLVED PER RE-SUBMITTAL RECEIVED 9-08-2016. 


5) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1) RESOLVED 9-12-2016.     