Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-1902
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

RETAIL STORE-TENANT IMPROVEMENT TO INCLUDE A, P, M, AND E.

CONTRACTOR TO PAY FOR INSPECTIONS-SP.   ***5/31/19  per Aaron Kiezer w/ Famous Footwear 314-873-8921 they never moved spaces at mall so cancel this permit... no refund*** 6/4/19 slo

Status: Closed
Project Name: FAMOUS FOOTWEAR STORE #3586
Review Type: Plumbing
Result: Correction
Result Date: 9/9/2016 9:18:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Sean Palmer

Phone: 343-8181

Email: PalmerSP@muni.org

Project: FAMOUS FOOTWARE

Review Number: 379106


1) STATUS: 9-09-2016 Comments to be addressed.


2) The following comments based upon the 2012 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. 


3)  P1.0               The P-2 public use lavatory requires an ASSE 1070 point of use mixing valve per UPC 421.2. MV at the water heater is not sufficient.


4) 4/P1.0             Water closets P1A & P1B are required to be separately vented per UPC 901.1. 


5) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter