RETAIL STORE-TENANT IMPROVEMENT TO INCLUDE A, P, M, AND E.
CONTRACTOR TO PAY FOR INSPECTIONS-SP. ***5/31/19 per Aaron Kiezer w/ Famous Footwear 314-873-8921 they never moved spaces at mall so cancel this permit... no refund*** 6/4/19 slo
Reviewed by: Bergstrom, Leigh W.
Phone: 343-8326
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Sean Palmer
Phone: 343-8181
Email: PalmerSP@muni.org
Project: FAMOUS FOOTWARE
Review Number: 379106
1) STATUS: 9-09-2016 Comments to be addressed.
2) The following comments based upon the 2012 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.
3) P1.0 The P-2 public use lavatory requires an ASSE 1070 point of use mixing valve per UPC 421.2. MV at the water heater is not sufficient.
4) 4/P1.0 Water closets P1A & P1B are required to be separately vented per UPC 901.1.
5) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1)