Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-1902
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

RETAIL STORE-TENANT IMPROVEMENT TO INCLUDE A, P, M, AND E.

CONTRACTOR TO PAY FOR INSPECTIONS-SP.   ***5/31/19  per Aaron Kiezer w/ Famous Footwear 314-873-8921 they never moved spaces at mall so cancel this permit... no refund*** 6/4/19 slo

Status: Closed
Project Name: FAMOUS FOOTWEAR STORE #3586
Review Type: Fire
Result: Correction
Result Date: 9/26/2016 8:04:33 AM

Comments:

 Code SectionReview CommentStatus
1_
Refer to Sheet A1.0. The code study notes the construction type as Type II-B. Please note the original construction type for the Dimond Center Tower was Type I-FR (UBC). Please revise accordingly.
Reference: IFC Section 105.4.2


2_
Refer to Sheet A1.0. Section IX (sic) of the code study notes no sprinkler modification. Walls have been demolished from this space as well as new ones being added. This will likely require adjustment of coverage requiring a separate systems permit (to be deferred). Please also note that fire alarm modifications will also likely be required and will need a systems permit (also to be deferred).
Reference: IFC Sections 105.7.1, 105.7.6


3_
Refer to Sheets A2.0, A4.0, E2.0. The plan shows Door D3 as an exit door, but there is no exterior egress lighting. Please provide.
Reference: IFC Section 1006.3 Item 5


4_
The plans do not identify the class and location of required fire extinguishers. Please note on the plans. A minimum of (3) 2-A class extinguishers is anticipated based on the occupancy hazard and the area of the tenant space.
Reference: IFC Section 906.1, 906.3, 906.5





Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter