Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-1902
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

RETAIL STORE-TENANT IMPROVEMENT TO INCLUDE A, P, M, AND E.

CONTRACTOR TO PAY FOR INSPECTIONS-SP.   ***5/31/19  per Aaron Kiezer w/ Famous Footwear 314-873-8921 they never moved spaces at mall so cancel this permit... no refund*** 6/4/19 slo

Status: Closed
Project Name: FAMOUS FOOTWEAR STORE #3586
Review Type: Electrical
Result: Correction
Result Date: 9/16/2016 11:46:52 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Electrical Comments



                                                                



Reviewed by: David Abuobaid                                                  Permit #: C16-1902



Phone: 343-8333                                                                       Date:
9/15//2016



Fax:     249-7775                                                                      



Email:  AbuobaidDH@muni.org                                               



Permit Manager: Sean Palmer



Phone: 343-8181



E Email:  Palmersr@muni.org



Project: Famous Foot
Ware (Fax: no fax provided)



__________________________________________________________________________



1. The following comments based on the 2014
National Electrical Code (NEC) must be resolved before a permit is issued. The
approval of plans and specifications does not permit the violation of any
section of the NEC or any federal, state or local regulations.



 



2.  AVAILABLE FAULT CURRENT:



Sheet E3.0 (Field Marking -
Available Fault Current). NEC Section 110.24 requires that service equipment be
legibly marked in the field with the maximum available fault current. The field
markings shall include the date the fault current calculation was performed.
The marking shall have sufficient durability to withstand the environment
involved. The marking of the available fault current shall be on the service
equipment and on every panel since panels are located on their individual units



 



3.  CIRCUIT DIRECTORY OR CIRCUIT INDENTIFICATION
ON FLOOR PLAN & PANEL SCHEDULES:



Sheet E3.0 (Panel
Schedules and Floor Plans Circuit Identifications). Panel schedules have many
circuits named rec-cash wrap, rec-phone board, LGT-2X4 sales, rec-managers desk.
Please note that these circuits should be individually identified with their
locations on floor plans and on the panel schedules according to NEC 408.4 for
circuit identifications.



 



4.  When
the above comments have been addressed, please update the electrical plans at
the MOA Plans Review Office with three (3) sets of revised electrical pages to
include clouded changes, electrical



Engineer’s stamp and signature.



ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter