Permit Number: E16-1847
Permit Type: Commercial Trade Permit - Alteration Electrical
Address: 5740 DE HAVILLAND AVE Anchorage
Location:
Work Description: Install head bolt heaters to Airfield Maintenance East lot for heavy equipment - AJC
Status: Closed
Project Name: AIRFIELD MAINTENANCE HEAD BOLT HEATERS
Review Type: Electrical
Result: Approved
Result Date: 9/1/2016 3:52:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

9/6/2016

the electrical plans have been corrected and approved

Electrical Comments



 



Reviewed by: David Abuobaid                                                  Permit #: E16-1847



Phone: 343-8333                                                                       Date:
9/1/2016



Fax:     249-7775                                                                      



Email:  AbuobaidDH@muni.org



Permit  Manager: Alec
Cervenka     



Phone: 343-8034



Email:  CervenkaAL@muni.org



Project: State of AK
Air Port (Fax: 266-2494)



____________________________________________________________________________________



1.  The
following comments based on the 2014 National Electrical Code (NEC) must be
resolved before a permit is issued. The approval of plans and specifications
does not permit the violation of any section of the NEC or any federal, state
or local regulations.



 



2. AMPERAGE INTERRUPTING
AMPACITY:



Sheet 3 of 3 (Panel Schedule AIC). The AIC calculation
on both panels shown to be 18,000 Amps. Please provide detail AIC calculation
for any panel has AIC rating higher than 10,000A.



 



3.  CIRCUIT DIRECTORY OR CIRCUIT INDENTIFICATION
ON FLOOR PLAN & PANEL SCHEDULES:



Sheet 3 of 3 (Panel
Schedules and Floor Plans Circuit Identifications). Panel schedules have many
circuits named head bolt heater receptacle. Please note that these circuits
should be individually identified with their locations on floor plans and on
the panel schedules according to NEC 408.4 for circuit identifications.



 



4.  AVAILABLE FAULT CURRENT:



Sheet 3 of 3 (Field Marking -
Available Fault Current). NEC Section 110.24 requires that service equipment be
legibly marked in the field with the maximum available fault current. The field
markings shall include the date the fault current calculation was performed.
The marking shall have sufficient durability to withstand the environment
involved. The marking of the available fault current shall be on the service
equipment and on every panel since panels are located on their individual units



 



5.  EXISTING
SERVICE LOAD CALCULATIONS:

Sheet 3 of 3. There are additional panel added. The plans have no calculations
for feeder loads for existing system. Provide service load calculation as
required per NEC Section 220.87.     



 



6.  When
the above comments have been addressed, please update the electrical plans at
the MOA



Plans Review Office with three (3) sets of
revised electrical pages to include clouded changes, electrical engineers stamp
and signature.