Permit Number: F16-1210
Permit Type: Commercial Trade Permit - Addition Fire
Address: 4901 SPENARD RD Anchorage
Location:
Work Description: 432 Sq Ft Addition(5A), and renovations to the lobby and new doors through out the Hotel - BWP
Status: Closed
Project Name: Child of Bldg App C16-1680
Review Type: Fire System
Result: Approved
Result Date: 9/6/2016 4:23:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Designer Dana Curtis does not have a state of Alaska electrical engineers permit. Update designers info on page FA0.00 to show fire system permit

2_Resolved
Update code reference on page FA0.20 to the 2010 NFPA 72

3_Resolved
Alarm and standby current draw do not match the spec sheets (sheet FA2.0)

4_Resolved
Starting voltages are 25 VDC and must be 20.4 vdc (sheets FA2.01/2.02/2.03) per 2010 NFPA 72 - 10.14.1

5_Resolved
Missing pull stations at exits 2010 ifc 907.4.2

6_Resolved
Missing smoke detection in areas that serve the sleeping rooms 2012 ifc 907.2.8.2

7_Resolved
ADA rooms do not have complete strobe coverage, missing in bathroom areas.

8_Resolved
how are you meeting ADA requirements for the room detectors vs general alarm for activation of the strobes?

9_Resolved
provide ceiling heights and room names per the 2012 ifc 907.1.2

10_Resolved
are there any walk in freezer or coolers that require notification



11_Resolved
there are strobes that are over spaced in the hallways (over 100 feet apart)

12_Resolved
plan review stopped, plans are incomplete.