Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-1725
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 300 DIMOND BLVD Anchorage
Location:
Work Description: Downsize of an existing FedEx Office tenant space. In the space to remain, there will be new interior finishes, new mop sink, new drinking fountain, and relocated lavatories. New drop ceiling, light fixtures, and relocated diffusers. New interior wall partition construction. New equipment, fixtures, and graphics. Work to include Architectural, Plumbing, Mechanical, and Electrical. - AJC
Status: Closed
Project Name: FEDEX OFFICE T/I
Review Type: Fire
Result: Approved
Result Date: 9/2/2016 7:42:18 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Please provide supporting documentation listed below to complete & approve the review:

1) Fire Extinguisher - show a min. of 1-2 extinguishers of at least a 2A 10BC sized rating , mounted in conspicuous locations, with current, state license tags affixed.
9/1/16 - Resolved. Items noted on Sheet A-3.0 // PANILO

2) Exit doors - thumbturns, double keyed cylinders, other type...on all exit doors ? Handle type, push bar, other ?
9/1/16 - Resolved. Revised sheet provided; updated door schedule on Sheet A-8.1 provided with compliant hardware noted // PANILO

3) Sprinkler permit appears to be req'd., & a separate permit & submittals required; Banners may block coverages.
9/1/16 - Resolved. Revised sheet provided; item noted on Sheet T-1.0 for deferred submittal // PANILO

4) Conspicuous unit # to be posted above main entry doors - easily readable to the street under all lighting/weather conditions; (suggest min. 6-10" high numerals, white vinyl peel ons, on outside of glass.
9/1/16 - Resolved. Revised sheet provided; item noted on Sheet A1.0 // PANILO

5) Emergency lighting unclear - no symbol for it was shown on submittals.
9/1/16 - Resolved. Revised sheet provided; updated plan on Sheet E-2.0 notes emergency lighting location. Note: Field verification of lighting levels may require additional emergency lights to be installed // PANILO





Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS