Permit Number:
F16-1206
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
3620 SHARON GAGNON LN Anchorage
Location:
Work Description:
FIRE HOOD 23 DEVICES - MJD
CHILD OF C16-1128
Status:
Closed
Project Name:
MAC HOUSING
Review Type:
Fire System
Result:
Approved
Result Date:
8/17/2016 2:06:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
The Guardian Fire System G-300-B being installed is a optional Nonrequired Fire Protection System per 2012 IFC 901.4.2. Guardian Units are listed to UL 300A and listing file number EX3940
2
AMC 23.10.104.9
Deferral of any submitted items shall have the prior approval of the building official. The registered design professional in responsible charge shall list the deferred submittals on the construction documents for review.
Resolved
Deferred submittal required for the fire alarm connection to the Guardian III fire suppression system for monitoring required per the 2009/2012 IFC 904.3.5.
Advisory Information: