Reviewed by: Bergstrom, Leigh W.
Phone: 343-8326
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Alec Cervenka
Phone: 343-8034
Email: CervenkaAJ@muni.org
Project: DIMOND CENTER MALL SOUTH ENTRY
Review Number: 377440
1) STATUS: 7-22-2016 Comments to be addressed. 8-09-2016 APPROVED.
2) The following comments based upon the 2012 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. RESOLVED 8-09-2016.
3) M1.1 The roof drains and rain leader piping may not be located within the stairway exit enclosure per IBC 1022.5. RESOLVED PER RE-SUBMITTAL RECEIVED 8-08-2016.
4) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1) RESOLVED 8-09-2016.