Permit Number: F16-1157
Permit Type: Commercial Trade Permit - Alteration Fire
Address: 2925 DEBARR RD Anchorage
Location:
Work Description: FIRE ALARM 71 DEVICES - MJD

CHILD OF C16-1599
Status: Closed
Project Name: MOB D STE. 240
Review Type: Fire System
Result: Approved
Result Date: 8/13/2016 12:55:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Rooms 151, 138, 147 have incomplete strobe coverage due to blockage by walls. Comply with 2010 NFPA 72 section 18.5.4.3

2_Resolved
Design must meet 2010 IFC with local amendments for Dba requirements. This will be verified at final