Permit Number: C16-1680
Permit Type: Commercial Building Permit - None BldgCombo
Address: 4901 SPENARD RD Anchorage
Location:
Work Description:

432 Sq Ft Addition(5A), and renovations to the lobby and new doors through out the Hotel - BWP


**CONTRACTOR PAID FOR 30 ADDITIONAL INSPECTIONS 1/4/2017. BWP**

Status: Closed
Project Name: COURTYARD MARRIOTT - EXERCISE ROOM EXPANSION
Review Type: Fire
Result: Approved
Result Date: 8/16/2016 9:52:24 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Please show on the plans the location(s) of existing fire extinguishers (FE), and anticipated location(s) of new FEs.
Reference: IFC Section 906

8/16/16 - Resolved. Existing FEC shown in corridor adjacent to addition within 75 ft. travel. Existing FEC shown adjacent to lobby space remodel; inspector to verify FEC within 75 ft. and FEs have current tags // PANILO


2_Resolved
Refer to Sheets E101, E102. The demo plan shows the emergency lighting in the being demolished, but the proposed plan does not show any new emergency lights. Please clarify.
Reference: IFC Section 1006.1

8/16/16 - Resolved. Existing emergency lights not being demolished per updated plan // PANILO