Permit Number: F16-1164
Permit Type: Commercial Trade Permit - Alteration Fire
Address: W 320 5TH AVE Anchorage
Location:
Work Description:

FIRE ALARM WITH 95 DEVICES - MJD


CHILD OF C16-1365

Status: Closed
Project Name: VICTORIA SECRET
Review Type: Fire System
Result: Approved
Result Date: 8/13/2016 11:06:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Strobe coverage is incorrect for the ceiling height, majority of the ceilings are over 10 feet and require 20 foot ceiling coverage for spacing per 2010 NFPA 72 Table 18.5.4.3.1 (b)

2_Resolved
Smoke detector in storage room on sheet FA101 does not cover the entire room.

3_Resolved
Fire Alarm System designers State of Alaska Permit for John Whisman 07-014 is currently expired. Provide a currently licensed designer.

4_Resolved
Provide ceiling elevations per 2012 IFC 907.1.2 and