Permit Number: X16-1685
Permit Type: Commercial Building Permit - ChangeOrdr BldgNew
Address: 1612 ANCHORAGE PORT RD Anchorage
Location:
Work Description: TEST RESULTS AND TEST CRITERIA FOR DELTA WESTERN PER CONVERSATION. AE
Status: Open
Project Name: Change Order of Bldg App C15-1161
Review Type: Structural
Result: Correction
Result Date: 8/4/2016 1:36:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

CHANGE ORDER STATUS
8/4/2016 - Change order reviewed. Comments issued.

1. The geotechnical report doesn't appear to give any actual recommendations, i.e. allowable bearing pressures. The report appears to give test compression strengths, but it is not clear how they relate to allowable bearing pressure (as based on the test results the native material would have an ultimate bearing strength of 82*144 = 1180-psf and at a factor of safety of 3 would give an allowable bearing pressure of around 4000-psf). The required mixed design has not been provided either (the report is based on specific percentages of cement, but does not indicate which to use). It's also not clear whether or not the mixture needs to be kept as a specific moisture while the mix is compacted and whether each layer needs to be "cured." It doesn't appear to discuss allowable lift heights. There are likely additional special inspection requirements for this procedure and the report does not appear to cover any of these either. Please provide a revised report with this information.