Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-1501
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: TENANT IMPROVEMENT, NEW WALL, FINISHES AND FIXTURES, MECH, ELEC AND PLBG INCLUDED-GJS
CONTRACTOR TO PAY INSPECTION FEES-GJS
***10/10/16 CONTRACTOR PRE-PAID FOR (10) INSPECTIONS.AE****
Status: Closed
Project Name: HOT TOPIC
Review Type: Electrical
Result: Correction
Result Date: 7/28/2016 3:57:14 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Architectural Comments



                                                                



 



Reviewed by: David Abuobaid                                                  Permit #: C15-1501



Phone: 343-8333                                                                       Date:
6/21/2016



Fax:     249-7775                                                                       Revised:
7/28/2016



Email:  AbuobaidDH@muni.org



Permit Manager: Bob Parker



Phone: 343-8319



E Email: ParkerRW@muni.org



Project: Hot Topic
(Fax: 277-1752)



__________________________________________________________________________



 



1.  The following comments based upon the 2014
International Building Code (IBC) must be resolved before a permit is issued.
The approval of plans and specifications does not permit the violation of any
section of the IBC or any federal, state or local regulations. 



 



2.  CODE ANALYSIS:



Sheet
T. Please address the following:



A:   The adopted international Building code are
all 2012 edition not 2009 edition.  



7/28/16
Corrected. Approved



B    The adopted National Electrical Code is
2014 edition not 2011 edition.



7/28/2016. Please
correct the code edition year. Please correction.



C.   What is the building construction type?



7/28/2016. The building
construction type is III-B, not I-B, please correct



 



3.  REQUIRED EXITING: 



Sheet
A1. The code study shows occupant load of 58 people. Please show on the plans
the two required exits, and the travel distance and the exit doors
hardware.   



7/28/2016. Since the
occupant load is 58, show the two required exit and travel distance,



7/28/2016. Please show
the two exit on the plans, Show travel distance and common path of egress. If
doo #5 is one of the required exit, show where the door exit to?



 



4.
When the above comments have been addressed, please update the plans at the MOA
Plans Review Office with three sets of revised architectural pages to include
clouded changes, engineers stamp and signature. 



         



 



ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter