Architectural Comments
Reviewed by: David Abuobaid Permit #: C15-1501
Phone: 343-8333 Date:6/21/2016
Fax: 249-7775 Revised:7/28/2016
Email: AbuobaidDH@muni.org
Permit Manager: Bob Parker
Phone: 343-8319
E Email: ParkerRW@muni.org
Project: Hot Topic(Fax: 277-1752)
__________________________________________________________________________
1. The following comments based upon the 2014International Building Code (IBC) must be resolved before a permit is issued.The approval of plans and specifications does not permit the violation of anysection of the IBC or any federal, state or local regulations.
2. CODE ANALYSIS:
SheetT. Please address the following:
A: The adopted international Building code areall 2012 edition not 2009 edition.
7/28/16Corrected. Approved
B The adopted National Electrical Code is2014 edition not 2011 edition.
7/28/2016. Pleasecorrect the code edition year. Please correction.
C. What is the building construction type?
7/28/2016. The buildingconstruction type is III-B, not I-B, please correct
3. REQUIRED EXITING:
SheetA1. The code study shows occupant load of 58 people. Please show on the plansthe two required exits, and the travel distance and the exit doorshardware.
7/28/2016. Since theoccupant load is 58, show the two required exit and travel distance,
7/28/2016. Please showthe two exit on the plans, Show travel distance and common path of egress. Ifdoo #5 is one of the required exit, show where the door exit to?
4.When the above comments have been addressed, please update the plans at the MOAPlans Review Office with three sets of revised architectural pages to includeclouded changes, engineers stamp and signature.