Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-1658
Permit Type: Commercial Building Permit - Building Sign
Address: E 300 DIMOND BLVD Anchorage
Location:
Work Description: INSTALLATION OF SIGNAGE. AE
Status: Closed
Project Name: ARCHITECTURAL GRAPHICS
Review Type: Structural
Result: Approved
Result Date: 7/26/2016 10:38:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
The attachment detail (labeled 8 of 19) does not identify the number of fasteners required (either total or spacing). It also shows fastening only at the top of the raceway. This is not necessarily stable against suction loads against the wall. Please clarify anchorage of the signage.
Reference: AMC 23.10.104.8.1





Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter