My Neighborhood
Contact Us
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
C16-1725
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
E 300 DIMOND BLVD Anchorage
Location:
Work Description:
Downsize of an existing FedEx Office tenant space. In the space to remain, there will be new interior finishes, new mop sink, new drinking fountain, and relocated lavatories. New drop ceiling, light fixtures, and relocated diffusers. New interior wall partition construction. New equipment, fixtures, and graphics. Work to include Architectural, Plumbing, Mechanical, and Electrical. - AJC
Status:
Closed
Project Name:
FEDEX OFFICE T/I
Review Type:
Fire
Result:
Correction
Result Date:
7/18/2016 10:30:22 AM
Comments:
Code Section
Review Comment
Status
1
_
Please provide supporting documentation listed below to complete & approve the review:
1) Fire Extinguisher - show a min. of 1-2 extinguishers of at least a 2A 10BC sized rating , mounted in conspicuous locations, with current, state license tags affixed.
2) Exit doors - thumbturns, double keyed cylinders, other type...on all exit doors ? Handle type, push bar, other ?
3) Sprinkler permit appears to be req'd., & a separate permit & submittals required; Banners may block coverages.
4) Conspicuous unit # to be posted above main entry doors - easily readable to the street under all lighting/weather conditions; (suggest min. 6-10" high numerals, white vinyl peel ons, on outside of glass.
5) Emergency lighting unclear - no symbol for it was shown on submittals.
Advisory Information:
ADA Compliance