Permit Number: C16-1720
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location:
Work Description:

Commercial T/I to include Architectural, Mechanical, and Electrical work.

Demolition of non-bearing walls, frame new non-bearing walls and storefront soffit. New flooring, plumbing and electrical demolition, new mechanical and electrical work, new lighting - AJC

Status: Closed
Project Name: VANILLA BOX T/I
Review Type: Architectural
Result: Approved
Result Date: 8/4/2016 4:06:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Architectural Comments



 



Reviewed by: David Abuobaid                                                  Permit #: C16-1720



Phone: 343-8333                                                                       Date:
7/19/2016



Fax:     249-7775



Email:  AbuobaidDH@muni.org



Permit  Manager: Alec
Cervenka     



Phone: 343-8034



Email:  CervenkaAL@muni.org



Project: Vanilla Box
(Fax: no fax provided) 



___________________________________________________________________________________



 



1. The following
comments based upon the 20012 International Building Code (IBC) must be
resolved before a permit is issued. The approval of plans and specifications
does not permit the violation of any section of the IBC or any federal, state
or local regulations. 



 



2.  WOOD STUDS USED IN WALLS IN THE 5TH
AVENUE MALL:



Sheet
A6.6 (Wall Types General Noes – Wood Studs). Note # 1 indicate option for
contractor to use either wood or metal studs for the interior wall. The 5th
avenue mall construction type is I-B. The wood in the interior wall is not permitted.
Please address. 



 



3.  DEFLECTING TRACKING:



Sheet
A6.6. The interior wall deflected tracking shall be listed assembly. Please address.



 



4.
When the above comments have been addressed, please update the plans at the MOA
Plans Review Office with three sets of revised architectural pages to include
clouded changes, engineers stamp and signature. 



         