Permit Number: C16-1709
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: Put 5 relocatable on site - BWP
Status: Issued
Project Name: WEST HIGH/ROMIG MIDDLE SCHOOL RELOCATABLES
Review Type: Fire
Result: Correction
Result Date: 7/11/2016 4:20:04 PM

Comments:

 Code SectionReview CommentStatus
1AMC 23.10.104.8.1Construction documents shall be of sufficient clarity to indicate the location, nature, and extent of the work proposed and show in detail that the work will conform to the provisions of this code.
Please address the following:
a. Please provide a scaled site plan showing the location of the proposed relocatable and the fire access lane. The most remote corner of the relo must be within 150 ft. of the fire access lane per IFC Section 503.1.1.
b. Please provide a plan layout of the relocatable showing the ingress/egress and the location of required fire extinguishers.