Permit Number: F16-1164
Permit Type: Commercial Trade Permit - Alteration Fire
Address: W 320 5TH AVE Anchorage
Location:
Work Description:

FIRE ALARM WITH 95 DEVICES - MJD


CHILD OF C16-1365

Status: Closed
Project Name: VICTORIA SECRET
Review Type: Fire System
Result: Correction
Result Date: 7/15/2016 10:41:00 AM

Comments:

 Code SectionReview CommentStatus
1_
Strobe coverage is incorrect for the ceiling height, majority of the ceilings are over 10 feet and require 20 foot ceiling coverage for spacing per 2010 NFPA 72 Table 18.5.4.3.1 (b)

2_
Smoke detector in storage room on sheet FA101 does not cover the entire room.

3_
Fire Alarm System designers State of Alaska Permit for John Whisman 07-014 is currently expired. Provide a currently licensed designer.

4_
Provide ceiling elevations per 2012 IFC 907.1.2 and