Click Here To Go Back To Permit Information
Permit Number:
F16-1160
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
W 320 5TH AVE Anchorage
Location:
Work Description:
129 DEVICES (SPRINKLERS), CHILD OF COMMERCIAL BUILDING PERMIT C16-1365-SP.
Status:
Closed
Project Name:
MALL-VICTORIA'S SECRET
Review Type:
Fire System
Result:
Approved
Result Date:
7/21/2016 11:24:00 AM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
Provide sprinkler coverage in display area - 2010 NFPA 13 section 8.1.1 does not apply to this situation (see handbook)
2
_
Resolved
Multiple areas are over spaced for the maximum coverage of 120 sq. ft. sprinkler coverage for ordinary hazard group II - pictures have been sent to bBlly with GMW
Advisory Information: