Permit Number:
F16-1157
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
2925 DEBARR RD Anchorage
Location:
Work Description:
FIRE ALARM 71 DEVICES - MJD
CHILD OF C16-1599
Status:
Closed
Project Name:
MOB D STE. 240
Review Type:
Fire System
Result:
Correction
Result Date:
7/13/2016 9:12:00 AM
Comments:
Code Section
Review Comment
Status
1
_
Rooms 151, 138, 147 have incomplete strobe coverage due to blockage by walls. Comply with 2010 NFPA 72 section 18.5.4.3
2
_
Design must meet 2010 IFC with local amendments for Dba requirements. This will be verified at final
Advisory Information: