Permit Number:
C16-1365
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
W 320 5TH AVE Anchorage
Location:
SUITE E15A 3RD FLOOR
Work Description:
TENANT IMPROVEMENT TO INCLUDE STRUCT,ARCH, ELEC, MECH, PLBG-GJS
INSPECTION FEES ARE DUE BEFORE ANY PERMIT ISSUANCES PER GJS 6/16/2016
10 Inspections added 06/20/16 - AJC
Status:
Closed
Project Name:
VICTORIA'S SECRET
Review Type:
Structural
Result:
Approved
Result Date:
6/16/2016 2:21:18 PM
Comments:
Code Section
Review Comment
Status
1
AMC 23.15.1704.1.4
Local amendment:
Unless otherwise approved by the building official, special inspectors shall be pre-qualified and approved by the building official before performing special inspection activities on any project within the Municipality. Special inspectors shall obtain pre-approval for each category of inspection they wish to perform.
Resolved
Please provide a letter from the Owner or Special Inspection Agency stating that the Owner has retained the Agency to provide required special inspections.
2
_
Resolved
Refer to Sheet A00.00, Detail E/S03.01. The code study incorrectly notes the construction type of the building as Type II-B; the mall is actually of Type I construction. The details note partition bracing to structure and deck, both of which will be protected by spray-applied fire-resistant material. Please coordinate with the architect on how the existing fire-resistance ratings will be maintained with the connections to deck/structure.
Reference: IEBC Section 702.1 (Section 603.1)
3
_
Resolved
Refer to Detail N/S03.01. The use of fire-retardant treated plywood is not permitted for Type I construction. Please revise by deleting reference.
Reference: IEBC Section 701.2 (Section 602.4)