Permit Number: C16-1452
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: INTERIOR FIT OUT FOR THE TENANT SPACE IN EXISTING INTERIOR MALL BUILDING INCLUDING DEMOLITION, CONSTRUCTION, MECHANICAL, ELECTRICAL AND PLUMBING, ETC. AE
Status: Closed
Project Name: VERIZON WIRELESS- DIMOND CENTER
Review Type: Fire
Result: Approved
Result Date: 6/3/2016 8:22:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Advisory comment: Per a phone conversation with architectural firm (John Ou) it was acknowledged that door 10 is required to be rated but was not noted on door schedule although it is in a 1 hr wall. Door shall either be 45 minute or 1 hr (if service corridor is an exit passageway). Architect office will notify contractor of the change, provide an e-mail to fire reviewer, & fire will advise architectural reviewer to mark field & MOA set of plans with a note requiring a rated door.




Advisory Information: