Architectural Comments
Reviewed by: David Abuobaid Permit #: C15-1501
Phone: 343-8333 Date:6/21/2016
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Bob Parker
Phone: 343-8319
E Email: ParkerRW@muni.org
Project: Hot Topic (Fax:277-1752)
____________________________________________________________________________
1. The following comments based upon the 2014International Building Code (IBC) must be resolved before a permit is issued.The approval of plans and specifications does not permit the violation of anysection of the IBC or any federal, state or local regulations.
2. CODE ANALYSIS:
SheetT. Please address the following:
A: The adopted international code are all 2012 editionnot 2009 edition.
B The adopted National Electrical Code is2014 edition not 2011 edition.
C. What is the building construction type?
3. REQUIRED EXITING:
SheetA1. The code study shows occupant load of 58 people. Please show on the plansthe two required exits, and the travel distance and the exit doors hardware.
4.When the above comments have been addressed, please update the plans at the MOAPlans Review Office with three sets of revised architectural pages to includeclouded changes, engineers stamp and signature.