Permit Type: Commercial Building Permit - None BldgAlter
Address: 2801 DEBARR RD Anchorage
Location:
Work Description: RENNOVATE 6TH FLOOR, NO CHANGE IN OCCUPANCY OR EGRESS-GJS
$ 1800.00 FOR INSPECTIONS PAID 8/16/2016-GJS
Status: Closed
Project Name: ONCOLOGY 6TH FLOOR
Review Type: Mechanical
Result: Correction
Result Date: 5/12/2016 11:22:31 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:



Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker

Phone: 343-8391

Email: ParkerRW@muni.org

Project: ONCOLOGY 6TH FLOOR

Review Number: 371980


1) STATUS: 5-12-2016 Comments to be addressed.


2) The following comments based upon the 2012 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. 


3) Provide structural, seismic and wind load calculations plus fastening details for IEF-6-1 & 2 to include the engineer's stamp and signature, on a deferred submittal basis.


4) M202              Soiled Utilities 642 and 655 have 1-hour enclosures and fire dampers at the duct penetrations. Rooms 610635 and 627 also have 1-hour enclosures per the Life-Safety Sheet A020 and do not have fire dampers at the duct penetrations. Please clarify.


5) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.   (23.10.104.8.1)