Permit Number:
F16-1041
Permit Type:
Commercial Trade Permit - Alteration Fire
Address:
E 800 DIMOND BLVD Anchorage
Location:
Work Description:
Fire Alarm. (633) devices - AJC
Status:
Issued
Project Name:
DIMOND CENTER MALL
Review Type:
Fire System
Result:
Approved
Result Date:
4/25/2016 3:30:00 PM
Comments:
Code Section
Review Comment
Status
Advisory Information:
Final Phase of Dimond Mall installation of NEW complete building fire alarm system from Honeywell; Add a pull in the outside Riser room on P. FA 12.13; All locations are subject to FIELD VERIFICATION upon final inspection & may require additions/alterations/etc. by Fire Official(s); Installer to ensure that there are no smoke hatches/dampers that are existing "stand alone" operation - that may need tying into new system;; Intelligibility will be checked upon Final inspection for clarity & understand-ability; Scope of project FINAL appears to require PRE scheduled Overtime when mall is not occupied...to be arranged with CO inspector well beforehand.